Important Notice To Pluris Wedgefield Customers

Late on the evening of August 21, 2026, a severe lightning strike caused damage to the water treatment facility, to include computers, SCADA, PLC’s, and communication equipment resulting in low water pressure for customers for approximately three hours. The SCADA system is purposely designed and programmed for an extreme event such as this to enter a fail-safe mode. The fail-safe mode ensures continuing operation of critical systems such as pumps and disinfection equipment. At no time did the system pressure drop below the Florida Department of Environmental Protection (“FDEP”) requirement of 20 psi. Our field crew immediately implemented emergency procedures and worked diligently to restore water pressure to affected customers as quickly as possible.

In addition, a 4-inch water main break occurred on Majestic Street, resulting in a temporary loss of water service to the 36 connections located along the street. Once the repair was completed, a precautionary Boil Water Advisory was issued, and affected addresses received the precautionary boil water notices by door tags. Our field crew followed established emergency procedures to restore water service and ensure that the appropriate precautionary boil water notices were provided to all affected customers.

Field operations staff were immediately deployed to the water treatment facility and the water main line break. The FDEP was noticed and updated through the events. Field operation staff assessed the lightning strike damages at the water treatment plant as well as repairing the watermain line, which was concluded at approximately 2 AM ET. Per FDEP requirements, bacterial water samples for laboratory testing were obtained and pending results expected later today (Tuesday August 25th) the precautionary boil water notice to the 36 residents should be cleared for the residents. The notice remains in effect until the laboratory provides the results and Pluris notifies the affected residents.

Our Customer Care number, 888-758-7471, is answered after hours by a service that was actively receiving calls throughout the low-pressure event. Due to the high volume of calls received, customers may have experienced a wait time. However, all calls were answered and promptly dispatched to our field crew, and customers were provided with available information regarding the emergency.

Please note that correspondence sent to our Customer Care email address, [email protected], is monitored during regular business hours and will be addressed by our representatives on the next business day.

We appreciate our customers’ patience and understanding as our field crews worked diligently to address these incidents and restore water service as quickly and safely as possible.

Total Trihalomethanes (“TTHMs”) and Haloacetic Acids (“HAA5”) at Wedgefield continue to be near Non-Detect

December 2024

Pluris Wedgefield (“Pluris”) is pleased to announce that the disinfectant by-products, total trihalomethane (“TTHM”) and Haloacetic Acids (“HAA5”) continue to be at or near non-detection limits in Wedgefield drinking water. The Federal Environmental Protection Agency (“EPA”) limit is 80 micrograms per liter and 60 micrograms per liter, for TTHM and HAA5, respectively.

Presented in the following table are the latest Florida Department of Environmental Protection (“FDEP”) compliance analytical laboratory testing results performed on December 6, 2024.

TTHM and HAA5 Test Results in Micrograms per Liter (µg/l)
(the Federal EPA Stage II TTHM Limit is 80 µg/l and the HAA5 Limit is 60 µg/l)

Date FDEP Determined Location Test Site
TTHM
FDEP Determined Location Test Site
HAA5
12/6/2024 2.40 3.12

The data continues to suggest that the conversion from chlorine to chlorine dioxide as the primary disinfectant has been a principal reason for the reduction of TTHM and HAA5, as chlorine dioxide, unlike chlorine does not create an environment for the formation of TTHM.

As always, any customers with questions or desiring to visit the water treatment plant facility are encouraged to contact Mr. Joe Kuhns, Regional Manager for Pluris. Mr. Kuhns will personally schedule a facility visit for any customer wanting to observe the chlorine dioxide treatment facility, as well as the entire drinking water treatment system. Mr. Kuhns can be reached via email at [email protected] or by telephone at (813) 526-0608.